>Product name | >HJDXH48/400 | >HJDXH-48/600 | >HJDXH-48/1000 |
>AC input | >380Vac, three-phase five-wire | >380Vac, three-phase five-wire | >380Vac, three-phase five-wire |
>AC input switch | >63A/3P×1 | >80A/3P×1 | >125A/3P×1 |
>AC output branch (optional) | >32A/3P×1; 16A/1P×3 | >32A/3P×1; 16A/1P×3 | >32A/3P×1; 16A/1P×3 |
>AC lightning protection | >Maintenance socket ×1 | >Maintenance socket ×1 | >Maintenance socket ×1 |
> Maximum system capacity Loadshunt |
>Class C, nominal 20kA -48V/400A; total 6 rectifier modules, total 2 photovoltaic modules |
>Class C, nominal 20kA -48V/600A; total 6 rectifier modules; total 6 photovoltaic modules |
>Class C, nominal 20kA -48V/1000A; total 12 rectifier modules, total 8 photovoltaic modules |
> Loadshunt |
>Power of the load: 100A×4 (fuse), 63A×6 (circuit breaker), 32A×6 (circuit breaker), 10A×2 (circuit breaker); Power of the battery: 63A×2 (circuit breaker), 16A×4 (circuit breaker), 10A×4 (circuit breaker) |
>Customer One: Power of the load: 160A×1 (fuse), 100A×3 (fuse), 63A×3 (circuit breaker); Power of the battery: 63A×2 (fuse), 32 A×2 (fuse) Customer two, customer three The branch circuit is the same as the customer’s one branch requirement. Customer Four: Power of the load: 125A×2 (circuit breaker), 32A×2 (circuit breaker); Battery power of: 16A×3 (circuit breaker) |
>Customer One: Power of the load: 160A×6 (fuse), 63A×3 (circuit breaker); Power of the battery: 100A×6 (fuse) Customer two, customer three The branch circuit is the same as the customerbegging; Customer Four: Power of the load: 125A×2 (fuse), 32A×2 (circuit breaker); Battery power of: 16A×3 (circuit breaker) |
>Battery shunt | >400Ax2 (fuse) | >600Ax2 (fuse) | >800Ax2 (fuse) |