Product model | HJDUM03/200 | >HJDUM03-48/400 | HJDUM03-48/600 |
AC input | 220Vac, Single Phase Three Line |
>380Vac,Three phase five wire system | 380Vac ,Three phase five wire system |
AC input switch | 63A/2P×2 Manual switching | >63A/3P×2 Manual switching | 100A/3P×2 Manual switching |
AC outputshunt (optional) | 16A/1P×5,10A/1P×4, Maintenance socket × 1 |
>16A/1P×5,10A/1P×4, Maintenance socket × 1 |
16A/1P×5,10A/1P×4, Maintenance socket × 1 |
AC lightning protection | Class C, nominal 20kA | >Class C, nominal 20kA | Class C, nominal 20kA |
Maximum system capacity | -48V / 200A: equipped with 4 rectifier modules | >-48V / 400A: equipped with 8 rectifier modules | -48V / 600A: equipped with 12 rectifier modules |
Loadshunt |
Client 1: Under load: 100A × 1 (circuit breaker), 16A × 1 (circuit breaker), 6A × 1 (circuit breaker); Battery power down: 25A × 1 (circuit breaker) Customer 2, customer 3 The shunt circuit is the same as that of the customer; Customer 4: Under load: 63A × 1 (circuit breaker); Battery power down: 10A × 2 (circuit breaker) |
||
Battery shunt | 125Ax4(circuit breaker) | ||
DC lightning protection | Rated flow 20kA | ||
Battery temperature cable | 1 piece of 3M long cable |